S7-1200 PLC是內建乙太網路的RJ-45接頭,因此非常適合應用在多台設備的網路連結。但是也不是無上限的連接,還是有硬體上的限制,所以各位看倌們在作網路架構時,要先弄清楚S7-1200 Ethernet port的規定,不然規劃錯了可是粉麻煩的呦。

此圖為同一個時間點最大的連接設備及數量:


已S7-1200 CPU 為中心,可連接的設備如下:

  • 3台人機設備 (3 connections for HMI to CPU communication)
  • 1台電腦編輯軟體  (1 connection for programming device (PG) to CPU communication)
  • 8台S7-1200 CPU (8 connections for S7-1200 program communication using the T-block instructions )(TSEND_C, TRCV_C, TCON, TDISCON, TSEND, TRCV)
  • 3台SIMATIC PLC 如S7-200,S7-300, S7-400  (3 connections for a passive S7-1200 CPU communicating with an active S7 CPU: The active S7 CPU uses GET and PUT instructions (S7-300 and S7-400) or ETHx_XFER instructions (S7-200). An active S7-1200 communication connection is only possible with the T-block instructions.)


------------------------------------------------------------------------------------------------------------------------------------------ Siemens SIMATIC PLC S7-400 S7-300 S7-1200 S7-200 LOGO HMI 西門子 自動化